You use the Vicon Connectivity node on the System tab of the Resources pane to configure Vicon connectivity units (eg, Vicon Locks), which are smart boxes that can be combined to create a distributed architecture.

See also:

Table of Contents
maxLevel2
minLevel2

Insert excerpt
Vantage:Vicon Vantage hardware
Vantage:Vicon Vantage hardware
nopaneltrue

Vicon Connectivity node context menu

You can select the following commands from the context menu displayed when you right-click on the Vicon Connectivity node:

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths25%, 75%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

CommandDescription
ReorderDisplay the Reorder Devices dialog box in which you can change the order in which Vicon connectivity units are displayed in the System Resources tree.
Reboot All Vicon Connectivity UnitsStop and restart all of the Vicon connectivity units in the Vicon system.

Scroll pagebreak

Vicon Lock node

Vicon Lock nodes are displayed under the Vicon Connectivity node on the System tab of the Resources pane when Vicon Nexus is connected to a Vicon system with at least one Lock unit and is in Live mode.

These connectivity unit nodes enable you to manage the identification and configuration settings for each Vicon Lock unit included in your Vicon system architecture.

For each connectivity unit the node name includes:

  • The device position number
  • Any display name specified in the Identification property
  • The device type listed in parentheses
    For example, #1 Name (Lock Lab).
    If either or both analog option cards are installed in the Lock Lab, the sample rates are displayed in brackets, for example, #1 Name [1000Hz/1000Hz] (Lock Lab), and an Analog Card (Slot 1) sub node is displayed as appropriate. If no analog source is selected, [No Source] is displayed after the device name.

See also:

Table of Contents
maxLevel3
minLevel3

Vicon Lock node context menu

You can select the following commands from the context menu displayed when you right-click on a node for a specific Lock unit.

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

CommandDescription
RebootStop and restart the selected device.
Reset TimecodeReset the Timecode to 00:00:00:00.

Scroll pagebreak

Anchor
ConnectivityProps
ConnectivityProps

Vicon Lock node properties

You can configure settings in the following sections of the Properties pane for the Vicon Connectivity node and nodes for any current Vicon connectivity units:

Table of Contents
maxLevel4
minLevel4

If you are using an analog card (this applies to all Lock Lab units), see also:

Identification section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
NameA user-defined display name for the entire set of Vicon connectivity units or for each individual connectivity unit.
Default: Blank
TypeThe device type
Default: Identified on connection.
Device IDThe unique identification number Vicon assigns to each connectivity unit during manufacture. The Vicon Connectivity node takes no value.
Default: Identified on connection

Scroll pagebreak

Status section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
ConnectedWhether or not the connectivity unit is currently connected to the Vicon system.
Default: Identified on connection
EnabledWhether or not the connectivity unit is currently enabled for use.
Default: Selected
Sync LockedWhether or not the connectivity unit is receiving and locked to the main (source) synchronization signal for the Vicon system.
Default: Identified on connection
Sync SourceWhether or not the connectivity unit is designated as the synchronization source for the Vicon system. For more information,
see Change the synchronization source in the Vicon Nexus User Guide.
Default: Identified on connection

Genlock section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
EnabledWhether or not Genlock functionality supported by the connectivity unit is currently enabled. If so, the scan rate of the incoming video signal from a PAL or NTSC video source is synchronized with Vicon cameras.
Default: Identified on connection
SourceThe genlock device source.
Default: Internal
Standard
The video standard of the external video source with whose incoming video signal scan rate the connectivity device is to synchronize the Vicon cameras. If one is not identified, None is displayed.
Default: Identified on connection
StatusThe status of the Genlock functionality: None, In Use, Ready To Use, Requires Other Frame Rate, Requires Device To Be Sync Source, or Requires Genlock.
Default: Identified on connection

Scroll pagebreak

Timecode section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
EnabledWhether or not Timecode functionality supported by an connectivity unit nis currently enabled. If so, the connectivity unit can be configured to trigger from or be time-stamped from a connected VITC (video) or LTC (audio) Timecode source.
Default: Identified on connection
SourceThe source designated as the main Timecode signal generator: VITC (external video device), LTC (external audio device), or Internal (Vicon connectivity unit).
Default: Internal
Dropped FramesWhether or not the connectivity unit is to adjust its internal counter to drop frames for the NTSC video standard. This option is available only if Internal is specified in Source. If selected, the separator character in the Timecode display in the Capture tools pane changes between a colon ( : ) for non-drop frames and semicolon ( ; ) for drop frames.
Default: Cleared
StandardThe video standard of the Timecode source from which the connectivity unit will trigger data capture or be time-stamped. If one is not identified, None is displayed.
Default: Identified on connection
StatusThe status of the Timecode functionality: None, In Use, Ready To Use, Requires Other Frame Rate, Requires Device To Be Sync Source, or Requires Genlock.
Default: Identified on connection

Scroll pagebreak

Sync Out section

The characteristics of a synchronization pulse that the connectivity unit is to generate to synchronize third-party hardware with the Vicon system (for technical details, see the Vicon Vantage Reference Guide). The general purpose output driver (*.gpo file) you specify here determines the output frequency of the synchronization pulse. You can select a driver for each of the sync outputs.

For each sync output, use the Browse for a folder button to navigate to the folder containing the .gpo files (by default, C:\Program Files\Vicon\Nexus2.# \GPO) and then used the drop-down list button to select the desired file (None, Duration, DV_Double, DV_Half, DV_Normal, or DV_Quarter):

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
Socket 1The .gpo configuration file to use to specify the synchronization signal for Powered Sync Output 1 in the rear panel of the connectivity unit.
Default: Blank
Socket 2The .gpo configuration file to use to specify the synchronization signal for Powered Sync Output 2 in the rear panel of the connectivity unit.
Default: Blank
Socket 3The .gpo configuration file to use to specify the synchronization signal for Powered Sync Output 3 in the rear panel of the connectivity unit.
Default: Blank
Socket 4The .gpo configuration file to use to specify the synchronization signal for Powered Sync Output 4 in the rear panel of the connectivity unit.
Default: Blank
Socket 5The .gpo configuration file to use to specify the synchronization signal for Sync Output 5 in the rear panel of the connectivity unit.
Default: Blank
Socket 6The .gpo configuration file to use to specify the synchronization signal for Sync Output 6 in the rear panel of the connectivity unit.
Default: Blank
Socket 7The .gpo configuration file to use to specify the synchronization signal for Sync Output 7 in the rear panel of the connectivity unit.
Default: Blank
Socket 8The .gpo configuration file to use to specify the synchronization signal for Sync Output 8 in the rear panel of the connectivity unit.
Default: Blank

Hardware section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
MAC AddressThe Media Access Control (MAC) address assigned to the connectivity unit during manufacture. This is a hexadecimal value in the format ##.##.##.##.##.##. The top-level entry for all connectivity units takes no value.
Default: Identified on connection
IP AddressThe Internet Protocol (IP) address assigned to the connectivity unit on the Vicon system Ethernet network. The top-level entry for all connectivity units takes no value.
Default: Identified on connection

Firmware section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
Firmware VersionThe version number of the firmware currently installed on the connectivity unit.
Default: Identified on connection
Firmware CompleteWhether or not the currently installed firmware is complete. If not, you can reprogram the firmware. See Update firmware in the Vicon Nexus User Guide.

Default: Identified on connection

Scroll pagebreak

Commands section

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
RebootStop and restart the connectivity unit.

Anchor
AnalogProps
AnalogProps

Analog card properties

Configuration section

You can configure the following settings in the Properties pane for an analog card connected to a connectivity unit:

Scroll tablelayout
sortDirectionASC
repeatTableHeadersdefault
widths20%, 80%
style
sortByColumn1
sortEnabledfalse
cellHighlightingtrue

PropertyDescription
Sampling Frequency (HZ)The sample rate for the analog card. The default analog sampling frequency is 1000 Hz and the corresponding default Vicon system frame rate is 100 Hz. The analog frequency must be an integer multiple of the frame rate and both must divide evenly into 135 MHz (the overall clock frequency). If you change the frame rate, the analog frequency may change automatically to meet these criteria. Similarly, if you enter an invalid analog sampling rate, its value is automatically adjusted to meet the criteria.
Default: Identified on connection
Channel CountThe number of channels provided by the analog card
Default: 64